In a HAZOP of a hydrocarbon separator, the team records the deviation 'more pressure', caused by the downstream control valve failing closed while the inlet stays open. The only safeguard listed is relief valve PSV-12. The process safety information shows PSV-12 was sized for the external fire case, and no one has checked its capacity against full inlet flow. How should the team treat PSV-12 for this cause?
Explanation
A safeguard counts in a HAZOP only if it is effective for the specific cause; a relief valve sized for a fire case may not pass the much larger load of a blocked outlet with full inlet flow, so the team should record a recommendation to verify the sizing rather than credit it. PSM requires process safety information that includes relief system design and design basis, and a PHA that addresses the engineering controls applicable to the hazards. Independence and a passed bench test are necessary but do not prove capacity, and an alarm does not make up for an undersized relief path. Source: 29 CFR 1910.119(d)(3)(i)(D) and (e)(3)(iii).Practise more questions like this