CSP practice question: Electrical guarding by elevation after a new working surface

Question of the Day for Tuesday, 29 September 2026

CSP · Advanced Application of Safety Principles Answer in HSE HUB Pro
Open 480-volt busbars run 9 feet above a warehouse floor and were accepted as guarded by elevation. A storage mezzanine is now built beneath them with its deck 4 feet above the floor, and general warehouse staff will pick stock from it. Under 29 CFR 1910.303(g)(2), what is the correct finding?
ANo longer guarded by elevation, since the bars are now 5 feet above a working surface; enclose, barrier or move them
BCompliant once warning signs at the mezzanine stair forbid entry by unqualified persons, since signs satisfy the rule
CStill compliant, since elevation is measured from the main floor and the bars remain 9 feet above that floor
DNo longer guarded, but staff may keep working there if trained in electrical hazards and told to stay 3 feet away

See the answer and the full explanation

Answers to Questions of the Day stay open for 30 days. This one, and every question in the bank, is answered and explained in HSE HUB Pro: unlimited practice by domain, the full 200-question mock exam and animated lessons.

See HSE HUB ProTry today's question, answer included

Studying for the CSP? The CSP11 blueprint explained · How to get the CSP · CSP practice exam by domain · All guides